Skip to content
MadocLocksmith Services
Open 24/7(289) 901-2787Open 24/7
Hands using a power driver at the end of a horizontal push bar on an open metal door. — Panic & Exit Hardware, Brampton
Person handling a lock cylinder at a workbench lined with cylinders, keys, small pin trays and blank key tags. — Commercial Rekeying, Brampton

Commercial · Brampton

Panic & Exit Hardware

The new access-control reader at the staff entrance works fine going in, but nobody has sorted out the door's exit side, and right now a card reader and a pushbar exist as two separate ideas.

Call (289) 901-2787

In plain words

Which device goes on a door depends on what the door already is. A single interior door usually takes a rim exit device and a simple pull or lever outside. Listed fire-exit hardware covers many tall, narrow-stile and fire-rated openings too, so a mortise or vertical-rod device is chosen for its latching arrangement or the door's own preparation, not from height or fire rating alone, and a fire-rated opening can never be held open by a mechanical dogging function. Reading the door correctly before ordering hardware is most of the job; fitting it well is the rest.

Sound familiar?

The fire inspector's note is blunt: the banquet hall's second exit still turns on a deadbolt, and the crowd it is rated to hold needs a door that opens under one motion, no key involved.

How the visit goes

Panic & Exit Hardware

How the visit goes

Technician holding two key fobs at a bench with a tablet and three fobs on a gray cloth, an open SUV behind.
Steel push bar with a latch housing, hinge plate, screws, screwdriver and tape measure on a worn bench beside an open box.
  1. Reading the door itself

    Every opening gets the same close look: whether it is fire-rated, which way it swings, how wide it is, and what preparation, if any, already exists in the door and frame from earlier hardware. A hollow-metal fire door takes a different device than a wood door in a non-rated partition, and a narrow-stile aluminum storefront door narrows the choice of device further still. Reading this correctly before anything is ordered is what keeps the installation from turning into a second visit once the wrong device arrives and does not fit the preparation already in the door.

  2. Mounting the device and fitting the strike

    Installation follows the device's own template so every hole lands where the manufacturer intended, rather than adapting the door to a device that does not quite fit. Fasteners are chosen to match what the template and the door's own construction call for, and where the device specifies through-fixings, they run all the way through the door rather than biting into the surface alone. The strike is set and reinforced so it holds the latch securely under normal use. The crossbar or touchpad is aligned so it sits at a comfortable height and releases evenly across its width, not only at one end.

  3. A written record for the next review

    The building now has a document naming every device fitted, its rating, the trim and any electrified function, and the tests each assembly passed on installation day. That record is what a fire inspector, an insurance reviewer or a new facilities manager will ask for, and having it ready saves reconstructing the history of a door from memory or from whatever sticker happens to still be on the case. It is worth keeping with the building's other life-safety paperwork.

Panic & Exit Hardware

In the van

  • Astragal and mullion hardware

  • Installation template and jig

  • Coordinator for door pairs

  • Strike and reinforcement

  • Force gauge

Technician and a seated person comparing two door lever handles on long backplates, one silver and one brass, at a kitchen table.

Panic & Exit Hardware

What affects the quote

  1. Signage and labelling

    Any exit signage or alarm labelling the opening needs is a small addition on its own, but it is named in the quote rather than assumed to already exist on the door.

  2. Fire-rated versus non-rated opening

    A fire-rated door needs hardware specifically listed for that assembly and installed to keep the rating intact, which is more involved than fitting a standard device to a non-rated door.

  3. Occupancy and code documentation needed

    A project with a fire inspector's note or a building official's requirement attached usually needs a more detailed written record than a straightforward upgrade an owner requests on their own initiative.

What to have ready

  • Which doors are involved, and are any of them fire-rated?
  • What is the room's intended use and approximate occupant load?
  • Has a fire inspector or building official already flagged a specific door?
Call (289) 901-2787

Panic & Exit Hardware: questions

Questions
Can one visit cover several doors in the same building?

Yes, and it is common. A building rarely has only one exit affected by an occupant-load or fire-rating question; stairway doors, assembly-room exits and any doors altered together during a renovation are usually assessed and fitted in the same visit, with one written record covering every device installed across the building.

Can I add a request-to-exit switch for my access-control system?

Yes. A request-to-exit switch is wired to signal the access-control panel that the pushpad or crossbar was actuated. Telling that apart from a forced or propped door usually means pairing it with a door-position contact and the panel's own logic, since the switch on its own only reports that the hardware was used. It sits alongside the mechanical device without changing how the crossbar or touchpad works, so the door still releases under a push even if the access-control system loses power.

When does a door actually need this hardware rather than a regular lock?

It comes down to occupancy and occupant load rather than preference. Rooms used for assembly, such as banquet halls, places of worship or gyms, and doors serving a stairway in a busier building, are where this hardware becomes the standard choice instead of a keyed lock on the exit side. A fire inspector or building official is the practical way to confirm whether a specific room has crossed that line.

Related services

Panic & Exit Hardware near you

Call(289) 901-2787

Request a visit

Or call (289) 901-2787 · open 24/7